Abstract
Purpose: The purpose of this paper is to review selected requirements for the design, installation, and maintenance of fixed fire extinguishing systems based on condensed aerosol generators, which are the most important component of aerosol fire extinguishing systems. Particular attention was paid to the hazards associated with the pH and corrosiveness of aerosol deposits on electronics, as well as the equally important hazards to humans associated with the size of the extinguishing aerosol particles.
Introduction: Fixed aerosol fire extinguishing devices and aerosol fire extinguishing kits, whose basic component is a condensed aerosol generator, are one example of specific solutions related to ensuring the safety of buildings. However, their design and operation differ from extinguishing systems that use extinguishing agents such as gases (e.g., CO2, N2, fluoroketones) or water-based agents (water, foam, or water mist). Therefore, the design, installation, and maintenance of such systems require special expertise and knowledge of potential hazards, including, for example, the entrapment of users or facility personnel in the extinguishing zone where aerosol discharge may occur.
Methodology: The article draws on theoretical research, such as: analysis of literature and legal documents, synthesis, generalization, inference, comparison, and analogy.
Conclusions: Condensed aerosol generators, which are an important component of aerosol fire extinguishing systems alongside other fire safety systems, have an impact on both the safety of buildings and the safety of users staying in the building. Considering the risks associated with aerosol discharge – reduced visibility, toxicity, thermal hazards – the competence of entities that declare to provide services in this area is very important in the design, installation, and maintenance of such systems. At later stages of the work, it will be crucial to determine the methods and possibilities for efficient and rapid removal of residues after the discharge of fire extinguishing aerosol in the protected extinguishing zone, so that the protected room can be restored to use as quickly as possible. It will be equally important to determine methods for removing aerosol residues from equipment, including, in particular, broadly understood electronics. The effective and safe use of SUG-A technologies requires not only knowledge of their physicochemical properties, but also a thorough risk assessment, knowledge of applicable regulations and standards, and appropriate qualifications of those involved in the design and maintenance of the installation.
Keywords: fire extinguishing, condensed aerosol generators, aerosol fire extinguishing kits, fire extinguishing agents
Type of article: review article
Bibliography:
- Polska Norma PN-EN 15276-2:2019-06 Stałe urządzenia gaśnicze – Aerozolowe zestawy gaśnicze – Część 2: Projektowanie, instalacja i konserwacja.
- Ustawa z dnia 12 września 2002 r. o normalizacji (t.j. Dz.U. 2015 poz. 1483).
- EN 12094-3:2003 Stałe urządzenia gaśnicze – Podzespoły urządzeń gaśniczych gazowych – Część 3: Wymagania i metody badań ręcznych urządzeń inicjujących i wstrzymujących.
- EN 54-4:1997 + AC:1999 + A1:2002 + A2:2006 Systemy sygnalizacji pożarowej – Część 4: Zasilacze. [5] Polska Norma PN-EN 54-13+A1:2020-05 Systemy sygnalizacji pożarowej – Część 13: Ocena kompatybilności i możliwości przyłączenia podzespołów systemu.
- Śliwiński R., Generatory skondensowanego aerozolu w ochronie przeciwpożarowej obiektów budowlanych. Część 1 – analiza dokumentów normatywnych i prawnych, „Safety & Fire Technology" 2024, 2, 102–123, https://doi.org/10.12845/sft.64.2.2024.7.
- Marine Accident Investigation Branch, Accident Investigation Report 9/2023, grudzień 2023 r.
- NFPA 2010, Edition 2025, Standard for Fixed Aerosol Fire- -Extinguishing Systems.
- Polska Norma PN-EN 13098:2007 Powietrze na stanowiskach pracy – Wytyczne dotyczące pomiaru mikroorganizmów i endotoksyn zawieszonych w powietrzu.
- Zhang X., Ismail M., Ahmadun F., Abdullah N., Hee C., Hot aerosol fire extinguishing agents and the associated technologies: A review, "Brazilian Journal of Chemical Engineering" 2015, 32, 03, 707–724, https://doi.org/10.1590/0104-6632.20150323s00003510.
- Sosnowski T.R., Aerozole wziewne i inhalatory, WIChiP PW, Warszawa 2012.
- Ustawa z dnia 24 sierpnia 1991 r. o ochronie przeciwpożarowej (t.j. Dz.U. 2025 poz. 188).
- Polska Norma PN-EN 16763:2017-04 Usługi w zakresie systemów ochrony przeciwpożarowej oraz systemów zabezpieczeń technicznych.
- Obwieszczenie Ministra Rozwoju i Technologii z dnia 28 marca 2023 r. w sprawie ogłoszenia jednolitego tekstu rozporządzenia Ministra Infrastruktury i Budownictwa w sprawie sposobu deklarowania właściwości użytkowych wyrobów budowlanych oraz sposobu znakowania ich znakiem budowlanym (Dz.U. 2023 poz. 873).
- Condensed aerosol fire extinguishing systems (CAFES) in-cabinet protection applications, Fire Protection Association (FPA), RISCAuthority, Form: IQ 5, Version 2 April 2023.
- PN-EN 15276-1:2019-07 Stałe urządzenia gaśnicze – Aerozolowe zestawy gaśnicze – Cześć 1: Wymagania i metody badań elementów składowych.
- Izak P., Kidoń A., Mastalarska-Popławska J., Mechanizm działania aerozolu gaśniczego, „Bezpieczeństwo i Technika Pożarnicza" 2017, 46, 2, 56–71, https:doi.org/10.12845/ bitp.46.2.2017.4.
- Rabajczyk A., Zielecka M., Gniazdowska J., Application of Nanotechnology in Extinguishing Agents, "Materials" 2022, 15, 8876, https://doi.org/10.3390/ma15248876.
- Sowa T., Analiza porównawcza stałych urządzeń gaśniczych, „Bezpieczeństwo i Technika Pożarnicza" 2010, 1, 113–132.
- Zbrożek P., Generatory aerozoli gaśniczych wytwarzanych pirotechnicznie, „Bezpieczeństwo i Technika Pożarnicza" 2006, 2, 4, 227–237.
- Rohilla M., Saxena A., Tyagi Y.K, Role of metal oxides on the performance of aerosol forming composites for fire extinguishing application, „Journal of Thermal Analysis and Calorimetry" 2022, 147, 8095–8108, https://doi.org/10.1007/s10973-021-11078-6.
- Kroca D., Klouda K., Application of aerosol extinguishing agents to increase infrastructure safety, IOP Conf. Ser.: Earth Environ. Sci. 444 012030, https://doi.org/10.1088/1755-1315/444/1/012030.
- Condensed Aerosol Fire Extinguishing Systems, Allianz Risk Consulting, Tech Talk, Volume 15, Allianz Global Corporate & Specialty SE, Reference TT 15/22/12, August 2018.
- NFPA 76:2024, Standard for the Fire Protection of Telecommunications Facilities.
- FM Global, Property Loss Prevention Data Sheets, Data Centers And Related Facilities, 5–32, Interim Revision July 2023.
- Guidance on Selection of Fire Protection Systems for Data Centers, euralarm, Zug, 17-01-2025.
- VdS 6003en:2025-06 (01), VdS Guidelines for Fire Protection Systems, Fire Protection Requirements for IT Rooms and Data Centres.
- Polska Norma PN-EN 50600-2-5:2021-08 Technika informatyczna – Wyposażenie i infrastruktura centrów przetwarzania danych – Część 2–5: Systemy zabezpieczeń.
- Uchwała nr 97 Rady Ministrów z dnia 11 września 2019 r. w sprawie Inicjatywy „Wspólna Infrastruktura Informatyczna Państwa" (t.j. M.P. 2021 poz. 1006).
- Komunikat Urzędu Komisji Nadzoru Finansowego dotyczący przetwarzania przez podmioty nadzorowane informacji w chmurze obliczeniowej publicznej lub hybrydowej z dnia 23 stycznia 2020 r.
- Sowa T., Analiza porównawcza stałych urządzeń gaśniczych cz. II, „Bezpieczeństwo i Technika Pożarnicza" 2010, 3, 141–146.
- Stałe urządzenia gaśnicze, Rodzaje, zastosowanie oraz ich wpływ na bezpieczeństwo pożarowe obiektów budowlanych, Polska Izba Ubezpieczeń, Warszawa 2015.
- Maintenance of condensed aerosol fire extinguishing systems/ equipment controlled by electronic detection systems, Euralarm Guidance, V1.0-EN, April 2023.